1. When installing rubber joints, super displacement installation is strictly prohibited.
2. The installation bolts should be symmetrical and gradually pressurized and torqued to prevent local leakage.
3. For working pressure above 1.6MPa, the installation bolts should have elastic pressure pads to prevent the bolts from loosening at work.
4. When installed vertically, both ends of the joint pipe should be supported by vertical force, and anti-pull-off devices can be adopted to prevent the work from being pulled off under pressure.
5. The installation part of rubber joint should be far away from heat source. Ozone area. It is strictly forbidden to expose to strong radiation and to use media that do not meet the requirements of this product.
6.Rubber joints are strictly forbidden to cut the surface and sealing surface by sharp instruments during transportation and handling.